Robustel GoRugged R3000 User Guide
RT_UG_R3000_v.2.0.0 17.01.2014 54 / 131
Confidential
OFF: Connect to GND (logic 0). When pin DI connects to GND, R3000 will
detect there is a DI alarm input.
ON: Open from GND (logic 1). When pin DI does not connect to GND, R3000
will detect there is a DI alarm input.
EVENT_COUNTER: under event counter mode.
Software filtering is used to control switch bounces.
Input from 0 to 10000ms.
Available when DI under Event Counter mode.
Input from 0 to 100. (0=will not trigger alarm)
It will trigger alarm when counter reaches this figure. After triggering alarm, DI
will keep counting but not trigger alarm again.
Available when DI under Event Counter mode.
In Event Counter mode, the channel accepts limit or proximity switches and
ted,
released.
Counter Start When
Power On
Available when DI under Event Counter mode.
Start counting as soon as possible on the modem when enable this option.
When R3000 need to work under Event Counter mode, user shall enable
receiving SMS command. Refer to another document SMS command of
R3000.
The SMS to receive upon triggering alarm. (70 ASIC II char max)
The SMS to receive upon recovering alarm. (70 ASIC II char max)
The alarm SMS will send to specified phone group.
Each phone group include up to 10 phone numbers.